Heating Load Calculator

Type the walls, windows, roof and floor with their U-values, the design temperatures and the air changes to get the heating power a building or room needs. Other modes give the heat of equipment, of an air flow, and warm-up times.

Enter your values

The heating power needed on the coldest design day.

Your values

The cold design temperature for your site from local climate data or the code (for example the 99.6% heating dry-bulb of the ASHRAE Handbook—Fundamentals).

Infiltration plus ventilation, from a blower-door test or the code. With heat recovery, use the share the recovery does not save.

Walls, windows, roof and floor

Areas of the parts that face outside (or an unheated space). U-values come from the maker, the plans or the energy certificate.

This unit is used in every row.

This unit is used in every row.

More options

EN 12831-1:2017 uses 0.34 Wh/(m³·K).

Added to the fabric loss when the U-values leave out junctions.

An extra share for warm-up or uncertainty, if your method uses one.

Optional: gives the load per square metre.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose Calculate.

Hour-by-hour warm-up simulation

Hour-by-hour warm-up simulation

Uses Warm-up and cool-down time above, with the daily outdoor swing under More options. The server integrates the room temperature hour by hour with a thermostat, so you see when the room is warm and how hard the heater works through two days.

More options

The calculator above works on your device. When you run a task in this section, Toolvito receives the values and result you submit to make the file or run the check. Download the result within one hour after the job finishes. Choose Delete files now to request earlier removal. The hourly cleanup normally removes files within one to two hours after completion.

How to work out a heat load

  1. In Heat loss of a building or room, list every part that faces outside with its area and U-value.
  2. Type the indoor temperature and the outdoor design temperature of your site.
  3. Type the heated volume and the air changes per hour (infiltration and ventilation).
  4. Press Calculate. The design heat load is the heating power for the coldest design day. Use the button under the result to carry the building to the warm-up mode.

The formulas

  • Fabric: Φ = Σ U × A × (θ_int − θ_e), plus an allowance for thermal bridges if your U-values leave them out.
  • Air: Φ = 0.34 × n × V × (θ_int − θ_e) in watts, with n air changes per hour and V in m³ (0.34 Wh/(m³·K) as in EN 12831-1:2017).
  • Equipment: all the electric power drawn ends up as heat; a UPS adds its losses, output × (1 ÷ efficiency − 1).
  • Air flow: Q = ρc × V̇ × ΔT.
  • Warm-up: with heat capacity C and heat loss coefficient H, T(t) = T∞ + (T0 − T∞) e^(−t ÷ τ) with τ = C ÷ H and T∞ = θ_e + Q ÷ H.

Worked example

Walls 95 m² at 0.30, windows 18 m² at 1.4, roof 70 m² at 0.18, floor 70 m² at 0.25 and a 2 m² door at 1.8 W/(m²·K) give U·A = 87.4 W/K. From 21 °C inside to −10 °C outside (31 K) the fabric loses 2,709 W.

175 m³ at 0.5 air changes per hour adds 0.34 × 0.5 × 175 × 31 = 922 W. The design heat load is 3,632 W (3.63 kW, 12,392 BTU/h).

Limits you should know

  • Design temperatures, U-values and air change rates depend on your site, building and code: none is built in.
  • This is the steady design loss in its simplest form. Manual J (ACCA) and the national annexes of EN 12831 add rules for ground floors, heated neighbours, intermittent heating and more. Heat gains from the sun and people are left out, which is on the safe side for heating.
  • Cooling loads need sun and internal gains: use the Cooling Load Calculator.