Heating Load Calculator
Type the walls, windows, roof and floor with their U-values, the design temperatures and the air changes to get the heating power a building or room needs. Other modes give the heat of equipment, of an air flow, and warm-up times.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to work out a heat load
- In Heat loss of a building or room, list every part that faces outside with its area and U-value.
- Type the indoor temperature and the outdoor design temperature of your site.
- Type the heated volume and the air changes per hour (infiltration and ventilation).
- Press Calculate. The design heat load is the heating power for the coldest design day. Use the button under the result to carry the building to the warm-up mode.
The formulas
- Fabric: Φ = Σ U × A × (θ_int − θ_e), plus an allowance for thermal bridges if your U-values leave them out.
- Air: Φ = 0.34 × n × V × (θ_int − θ_e) in watts, with n air changes per hour and V in m³ (0.34 Wh/(m³·K) as in EN 12831-1:2017).
- Equipment: all the electric power drawn ends up as heat; a UPS adds its losses, output × (1 ÷ efficiency − 1).
- Air flow: Q = ρc × V̇ × ΔT.
- Warm-up: with heat capacity C and heat loss coefficient H, T(t) = T∞ + (T0 − T∞) e^(−t ÷ τ) with τ = C ÷ H and T∞ = θ_e + Q ÷ H.
Worked example
Walls 95 m² at 0.30, windows 18 m² at 1.4, roof 70 m² at 0.18, floor 70 m² at 0.25 and a 2 m² door at 1.8 W/(m²·K) give U·A = 87.4 W/K. From 21 °C inside to −10 °C outside (31 K) the fabric loses 2,709 W.
175 m³ at 0.5 air changes per hour adds 0.34 × 0.5 × 175 × 31 = 922 W. The design heat load is 3,632 W (3.63 kW, 12,392 BTU/h).
Limits you should know
- Design temperatures, U-values and air change rates depend on your site, building and code: none is built in.
- This is the steady design loss in its simplest form. Manual J (ACCA) and the national annexes of EN 12831 add rules for ground floors, heated neighbours, intermittent heating and more. Heat gains from the sun and people are left out, which is on the safe side for heating.
- Cooling loads need sun and internal gains: use the Cooling Load Calculator.