Toolvito

Works on this device

Surge Protection Checklist

Choose the kind of site and what it has. The tool makes a list of points to check and questions to ask a qualified installer about surge protective devices (SPDs). You can tick the points, add notes, print the list or download it.

Enter your values

Choose the kind of site, what you are doing and what the site has. The tool makes a list of points to check and questions to ask a qualified installer.

Your values

For the heading of the list, for example "Workshop, main board".

This changes the names of the standards in the list. Choose "I am not sure" to see both.

This is off unless you turn it on. Saved entries stay in this browser only. Untick the box to delete them.

Your values are worked out in this browser. They are not sent to a server.

Your result will show here

Fill in the values, then choose the button below them.

How to use this checklist

  1. Choose the kind of site, what you are doing, and the standards used where you live. Choose "I am not sure" to see both sets of names.
  2. Tick the boxes that are true for your site, such as an overhead supply, a solar PV system or data cables that enter the building.
  3. Choose Make the checklist. Print the list, copy it, or download it as a text file or a CSV file.
  4. Choose Tick and edit this list to move the list into rows. There you tick what is done, write what you read on a label or what the installer said, and add your own points.
  5. Tick Save my entries on this device to keep the list, its ticks and your notes in this browser.

How the list is made

The tool holds a set of points. Each point belongs to one part of the list and has a rule that says when it applies. For example, the point about the impulse current of a Type 1 device is added only for a building with a lightning protection system or an overhead supply, and the points about plug-in protectors only when you use them.

The list has six parts: Know your site, Ratings to read on the device label, Where the devices go, Earthing and bonding, Questions for the installer and Indicator, replacement and records.

The ratings on a device label, in plain words

The ratings of a surge protective device are defined by product standards: IEC 61643-11 (EN 61643-11 in Europe) and UL 1449 in the United States and Canada. The table gives each rating in plain words. The label and the data sheet of the device are what count.

Ratings of a surge protective device
Rating On IEC labels On UL labels What it means
Maximum continuous operating voltage Uc MCOV The highest steady voltage the device can stay connected to
Protection voltage Up (voltage protection level) VPR (voltage protection rating) The voltage the device lets through in the standard test; lower lets less through
Nominal discharge current In In The surge current the device is tested to take many times
Maximum discharge current Imax Not a UL 1449 rating The largest surge current the device is tested to take once
Impulse current Iimp (Type 1 devices) Not a UL 1449 rating A test current that stands for part of a lightning strike
Short-circuit current rating Isccr SCCR The largest fault current of the supply at which the device may be installed
Type Type 1, 2 or 3 Type 1, 2 or 3 Which tests the device passed and where in the installation it belongs

Worked example

For a home with new protection planned, IEC and EN standards, data cables that enter the building, sensitive equipment and plug-in protectors, the list has 37 points: 5 to know the site, 10 about the ratings on the label, 4 about where the devices go, 5 about earthing and bonding, 7 questions for the installer, and 6 about the indicator, replacement and records.

In the tick list, with 6 points and 3 of them ticked, the result shows 3 done, 3 still to do and 50%.

Limits you should know

  • This checklist is for understanding and for preparing a talk with an installer. It is not a design. Electrical work must follow the local code and be done or checked by a qualified electrician.
  • The tool does not choose a device, a rating or a place for it, and it gives no installation steps.
  • The plain-word meanings are short. The exact definitions and test methods are in the standards, and they are revised.
  • Wiring rules for surge protection differ by country and edition. Ask the installer which rules apply where you live.
  • No device stops every surge. A direct lightning strike can cause damage even with protection.
  • The list is general. Add the points that your installer, your insurer or the maker of your equipment gives you.

Related tools