Control Valve Sizing Calculator
Find the flow coefficient (Kv or Cv) that a control valve needs to pass your flow at your pressure drop, and check whether the flow would be choked. Every valve factor comes from the maker's data that you type.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use this calculator
- Choose Liquid, Gas or steam, or Valve authority.
- Enter the flow and the inlet and outlet pressures, and say whether they are gauge or absolute pressures.
- For a liquid, enter its relative density (1 for water). For the choked-flow check, choose water (the tool works out the vapour pressure from the temperature) or type the vapour pressure and FF of your liquid, and type FL from the valve maker.
- For a gas or steam, enter the inlet density (for steam, from steam tables) or let the tool work it out for an ideal gas, the ratio of specific heats γ and the valve factor xT from the maker.
- Choose Calculate. Under More options you can type the rated Kv or Cv of a valve to see how much of it the duty needs.
The formulas (IEC 60534-2-1, the same as ANSI/ISA-75.01.01)
- Liquid: Kv = Q × √((ρ1 ÷ ρ0) ÷ Δp) with Q in m³/h and Δp in bar; Cv = Q × √((ρ1 ÷ ρ0) ÷ Δp) with Q in US gpm and Δp in psi. Cv = 1.156 × Kv.
- Choked liquid flow: the flow stops rising when Δp reaches FL² × (p1 − FF × pv); that limit is then used for Δp. For water, FF = 0.96 − 0.28 × √(pv ÷ pc) with pc = 22.064 MPa.
- Gas and steam: W = N6 × Kv × Y × √(x × p1 × ρ1), with W in kg/h, p1 in bar (absolute), ρ1 in kg/m³, x = Δp ÷ p1 and N6 = 31.6.
- Expansion factor: Y = 1 − x ÷ (3 × Fγ × xT), with Fγ = γ ÷ 1.40. The flow is choked when x reaches Fγ × xT; then x = Fγ × xT and Y = 2/3.
- Valve authority: N = Δp of the valve ÷ (Δp of the valve + Δp of the rest of the circuit), at the design flow.
Worked examples
Water: 20 m³/h at 20 °C, from 5 bar to 3.5 bar gauge. Δp = 1.5 bar, so Kv = 20 × √(1 ÷ 1.5) = 16.33 and Cv = 18.88. With FL = 0.9 the choked limit is 0.81 × (6.013 − 0.957 × 0.0234) = 4.853 bar, well above 1.5 bar, so the flow is not choked.
Steam: 1,500 kg/h of saturated steam at 6.013 bar absolute (3.17 kg/m³), dropping 1.5 bar, with γ = 1.3 and xT = 0.7. x = 0.2494, Fγ = 0.9286, Y = 1 − 0.2494 ÷ (3 × 0.9286 × 0.7) = 0.8721, so Kv = 1,500 ÷ (31.62 × 0.8721 × √(0.2494 × 6.013 × 3.17)) = 24.94 and Cv = 28.84.
Authority: a valve that takes 30 kPa in a circuit whose pipes and coil take 30 kPa has an authority of 0.5. For 2 m³/h of water at that drop it needs Kv = 2 × √(1 ÷ 0.3) = 3.651.
Limits you should know
- FL, xT and the rated Kv or Cv belong to one valve at one opening. Take them from the valve maker; the example values are only for trying the tool.
- The relations are for turbulent flow, with the valve the same size as the pipe. Reducers next to the valve (FP, FLP), viscous liquids (FR), two-phase flow, noise and the valve characteristic are not worked out.
- Cavitation can start before the flow is choked, and a liquid flashes when the outlet pressure is below its vapour pressure. The tool flags flashing; the maker's data shows where cavitation starts.
- To turn a Kv into a Cv or back, or to find the flow through a valve of known Cv, use the Valve Cv Calculator and the Valve Kv Calculator.
- This is a sizing estimate for the values you type, not a valve selection. The valve maker or a qualified engineer chooses and checks the valve. This is not professional advice.