Pump Affinity Laws Calculator
The affinity laws tell how a centrifugal pump changes when its speed changes or its impeller is trimmed: the flow with the ratio, the head with its square and the power with its cube. Use them, check them against a system with a static lift, and see the power saved.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use this calculator
- Choose a new speed, a trimmed impeller, the diameter for a duty point from the pump curve, a new speed in a system with static head, or the saving of a slower speed.
- Enter a point of the pump now: its flow, head and, if you know it, its power. Speeds can be in any unit (rpm, Hz or percent), the same for both.
- For the system check, add the static head of the system and the shut-off head of the pump (the head at zero flow on its curve).
- For the saving, enter the input power now, the hours of use and, if you want the cost, your price for one kWh.
- Choose Calculate. The result shows the new values, the ratios and the working.
The formulas
- Speed: Q₂ = Q₁ × (N₂ ÷ N₁), H₂ = H₁ × (N₂ ÷ N₁)², P₂ = P₁ × (N₂ ÷ N₁)³.
- Impeller trim at the same speed: Q₂ = Q₁ × (D₂ ÷ D₁), H₂ = H₁ × (D₂ ÷ D₁)², P₂ = P₁ × (D₂ ÷ D₁)³, an approximation for small trims.
- Diameter for a duty point: the parabola H = c × Q² through the duty point (c = H₂ ÷ Q₂²) meets the full curve at point A; then D₂ = D₁ × Q₂ ÷ Q_A.
- System with static head: system H = H_s + k × Q²; pump taken as H = H₀ × r² − a × Q² with r = N ÷ N₁. They meet at Q = √((H₀ r² − H_s) ÷ (a + k)). The least speed that moves any liquid is N₁ × √(H_s ÷ H₀).
- Saving: power at the new speed = power now × (N₂ ÷ N₁)³; energy = power × hours; cost = energy × your price.
Worked examples
A pump gives 50 m³/h at 40 m at 2,900 rpm. At 2,320 rpm (a ratio of 0.8) it gives 40 m³/h at 25.6 m, and its power falls to 0.512 times, 51.2 %.
Trimming its 250 mm impeller to 235 mm (6 % cut away) gives about 47 m³/h at 35.34 m.
In a system with a static head of 15 m and a shut-off head of 55 m, the same slowdown gives 35.5 m³/h at 27.6 m, not 40 m³/h, and the hydraulic power falls to 49.1 % of now. Below 1,514 rpm the pump moves no water.
A pump that takes 15 kW, run 8 hours a day all year, uses 43,800 kWh. At 80 % speed it takes 7.68 kW and saves 21,374 kWh a year; at 0.15 for one kWh that is 3,206.16 a year.
Limits you should know
- The affinity laws are an ideal model of one pump. They take the efficiency as the same at matching points; it changes a little with the speed and more with a large trim.
- The trimming rule holds only for small trims of the same impeller (a common guide is up to about 10 %). Never trim below the smallest diameter on the maker's curve; the maker's curves decide.
- With a static head, the plain affinity laws overstate the flow and the saving at a lower speed. The system choice uses a parabola for the pump curve, which is an estimate; with the maker's curve the Pump Head Calculator finds the operating point.
- The price, the power and the hours are your figures; no tariff is built in, and the example price is only for trying the tool. Drive losses are not counted.
- The power for a flow and head is on the Pump Power Calculator, and the efficiency on the Pump Efficiency Calculator.
- The results are arithmetic for the values you type, not a pump selection. This is not professional advice.