Heat Exchanger Calculator
Work out the area a heat exchanger needs for four temperatures (LMTD method), the outlet temperatures of an exchanger you have (ε-NTU method), the heat duty or flow of one fluid, the overall heat transfer coefficient with fouling, or the velocity and pressure drop in the tubes.
Enter your values
Check these values
Your values are worked out in this browser. They are not sent to a server.
Your result will show here
Fill in the values, then choose Calculate.
Your result
How it was worked out
How to use the heat exchanger calculator
- To size an exchanger: choose the flow arrangement, type the four temperatures, the flow and specific heat of one fluid (or the duty) and U. You get the duty, the LMTD, the correction factor F, the area and the flow the other fluid needs; with a tube size or a plate area also the number of tubes or plates.
- To rate an exchanger you have: type its area and U, the two inlet temperatures and both flows. You get the effectiveness, the duty and both outlet temperatures. For a steam heater choose that the hot fluid condenses.
- The other modes work out a heat duty or flow (Q = ṁ cp ΔT), the overall coefficient U from film coefficients, the wall and fouling, and the tube-side velocity and pressure drop.
- The box under the result repeats a sizing, rating or duty with the property data of real fluids at every temperature (also boiling and condensing) and draws the temperature profile.
The formulas
- Heat duty: Q = ṁ cp (T_in − T_out) of either fluid; both must give the same Q.
- LMTD = (ΔT₁ − ΔT₂) ÷ ln(ΔT₁ ÷ ΔT₂), with ΔT₁ and ΔT₂ the differences between the fluids at the two ends. Area A = Q ÷ (U F LMTD).
- F corrects the counterflow LMTD for shell-and-tube and crossflow exchangers. It comes from the ε-NTU relations, the same as the Bowman, Mueller and Nagle (1940) charts. Values below about 0.75 point to a poor arrangement.
- ε-NTU: NTU = U A ÷ Cmin with C = ṁ cp; the effectiveness ε of the arrangement (Kays and London) gives Q = ε Cmin (T_hot,in − T_cold,in).
- U with fouling on a tube: 1/U = 1/hₒ + Rfₒ + dₒ ln(dₒ/dᵢ) ÷ 2k + Rfᵢ dₒ/dᵢ + dₒ ÷ (hᵢ dᵢ).
Worked example
Water at 2 kg/s is cooled from 90 to 60 °C by water warmed from 20 to 50 °C (cp 4.18 kJ/(kg·K)). Q = 2 × 4.18 × 30 = 250.8 kW. In counterflow both ends differ by 40 K, so LMTD = 40 K, and with U = 1,000 W/(m²·K) the area is 250,800 ÷ (1,000 × 40) = 6.27 m².
A shell-and-tube exchanger with one shell pass needs F = 0.898 here, so 6.98 m². The same exchanger rated with 10 m² gives an effectiveness of 0.545 and outlets of 51.9 and 58.1 °C.
Limits you should know
- U is taken as typed and the same everywhere; it is the largest uncertainty. Film coefficients from correlations, shell-side flow and mechanical design (tube thickness, expansion, TEMA rules) are not worked out here.
- The page uses one specific heat for each fluid; when a fluid boils or condenses or its cp changes much, use the server box.